89
The table below shows the editable properties in these built-in control programs:
#1 100% outside air unit
#2 Air source heat pump - reverse to heat
#3 Air source heat pump - reverse to cool
#4 Air source heat pump - intermittent fan - reverse to heat
#5 Air source heat pump - intermittent fan - reverse to cool
#6 Convective/fin tube heater
#7 Fan coil unit - 2-speed fan, modulated or 2-stage cooling and heating
#8 Fan coil unit - 3-speed fan, 2-stage or modulated cooling, 1-stage or modulated heating
#9 Fan coil unit - 3-speed fan, 1-stage or modulated cooling, 2-stage or modulated heating
#10 Fan coil unit - intermittent fan, modulated or 2-stage cooling and heating
#11 Fan coil unit - heat controlled fan, modulated or 2-stage cooling and heating
#12 Unit ventilator
Used in control program
Properties
Units
Default
1
2
3
4
5
6
7
8
9
10
11
12
Setpoints
Unocc Clg Setpt
Deg 85
X
X
X
X
X
X
X
X
X X
X
X
Occ Clg Setpt
Deg 74
X
X
X
X
X
X
X
X
X X
X
X
Occ Htg Setpt
Deg 70
X
X
X
X
X
X
X
X
X X
X
X
Unocc Htg Setpt
Deg 55
X
X
X
X
X
X
X
X
X X
X
X
Color Band Width
Deg 2
X
X
X
X
X
X
X
X
X X
X
X
Color Hysteresis
Deg 0.5
X
X
X
X
X
X
X
X
X X
X
X
PID
Htg P Gain
%
20
X
X
X
X
X
X
X
X
X X
X
X
Htg I Gain
%
2
X
X
X
X
X
X
X
X
X X
X
X
Htg D Gain
%
0
X
X
X
X
X
X
X
X
X X
X
X
Htg PID Interval
Sec
60
X
X
X
X
X
X
X
X
X X
X
X
Htg PID Ramp Time*
Sec
240
X
X
X
X
X
X
X
X
X X
X
X
Htg PID Deadband**
Deg 0.5
X
X
X
X
X
X
X
X
X X
X
X
Clg P Gain
%
20
X
X
X
X
X
X
X
X X
X
X
Clg I Gain
%
2
X
X
X
X
X
X
X
X X
X
X
Clg D Gain
%
0
X
X
X
X
X
X
X
X X
X
X
Clg PID Interval
Sec
60
X
X
X
X
X
X
X
X X
X
X
Clg PID Ramp Time*
Sec
240
X
X
X
X
X
X
X
X X
X
X
Clg PID Deadband**
Deg 0.5
X
X
X
X
X
X
X
X X
X
X
Editable properties