![Automated Logic RC642 Technical Instructions Download Page 20](http://html.mh-extra.com/html/automated-logic/rc642/rc642_technical-instructions_3021520020.webp)
16
Download the following items to the Room Controller's battery-backed memory:
Item
Notes
Control program
Must be in
WebCTRLx.x\webroot\
<system_name>
\programs
.
DRV_RCM driver
Must be in
WebCTRLx.x\webroot\
<system_name>
\drivers
.
NOTE
To verify that you have the driver's latest version, go to
http://accounts.automatedlogic.com/download, then select
Drivers
>
ExecB
. Compare the latest version to the Room
Controller's driver in SiteBuilder.
Editable properties
Schedules
If you change any of these items or the Room Controller's address after the initial
download, you must download again. The first download takes longer than subsequent
downloads.
CAUTIONS
•
The Room Controller will lose stored data when you download.
•
Equipment controlled by the Room Controller will shut down and restart when you
download.
You download the controller from WebCTRL. If your network is complete, you can
download from any network browser. If not complete, connect a laptop with a local copy of
the system database to the Room Controller's local access port. See
To communicate
through the local access port
(page 23).
1
On WebCTRL's
NET
tree, select the controller.
2
Click
Downloads
.
3
Do one of the following:
○
If the controller is in the Downloads list, go to step 4.
○
If the controller is not in the list:
a. Click
Add
.
b. In the pop-up, select the controller.
c. Select
All Content
.
d. Click
Add
.
e. Click
Close
.
4
Select the controller in the Downloads list.
5
Click
Start
.
NOTES
•
If the download fails, locate and resolve the problem, then retry the download.
•
You can also download a controller from the
Devices
page.
Downloading the Room Controller
To download in
WebCTRL