![Automated Logic RC642 Technical Instructions Download Page 16](http://html.mh-extra.com/html/automated-logic/rc642/rc642_technical-instructions_3021520016.webp)
12
Shielding
If shielded, Aluminum/Mylar shield (100% coverage) with TC
drain wire
UL temperature rating 32–167°F (0–75°C)
Voltage
300 Vac, power limited
Listing
UL: NEC CL2P, or better
1
Remove power from the Room Controller.
2
Partially cut, then bend and pull off the outer jacket of the Rnet cable(s). Do not nick
the inner insulation.
3
Inner insulation
Outer jacket
Foil shield
.25 in.
(.6 cm)
4
Strip about .25 inch (.6 cm) of the inner insulation from each wire.
5
Wire each terminal on the Room Controller's
Rnet
port to the terminal of the same
name on the RS room sensor.
NOTE
If using shielded wire, connect the shield wire and the ground wire to the
Gnd
terminal.
Wire to
Rnet
R
ne
t +
G
ro
un
d
R
ne
t –
+1
2V
6
Apply power to the Room Controller.
To wire an RS
room sensor to
the Room
Controller