14
NOTE
Connect the shield wire to the
GND
terminal with the ground wire.
Dry
contact
Gnd
Gnd
Gnd
Any input
Input 3 & 4 only
Input 3 & 4 only
Input 3 & 4 only
Gnd
Gnd
Thermistor
24 Vdc
half-wave
power
supply
2 wire
3 wire
4 wire
Out
V+
Gnd
Out
V+
n/c
Out +
Out -
V+
Gnd
0-5 Vdc
0-5 Vdc
0-5 Vdc
4
Set the
UI-3
and
UI-4
jumpers.
If...
Is used for...
Then...
Input 3
Dry contact
Put on
UI-3 Jumper
0-5 Vdc
Remove
UI-3 Jumper
Input 4
Dry contact
Put on
UI-4 Jumper
0-5 Vdc
Remove
UI-4 Jumper
5
Connect the digital output wiring to the screw terminals on the Room Controller and to
the controlled device.
24 Vac
Motor
Valve
Any DO
Any DO
24 Vac in
Com
Control
Module
Power
Any DO