11
5
Set the communication type and baud rate.
For...
Set DIP switch 4 to...
Set DIP switches 1 and 2 to the appropriate
baud rate...
ARC156
Off
N/A. Baud rate will be 156 kbps regardless
of the DIP switch settings.
MS/TP
On
9600
1 2
1 2
1 2
1 2
19200
38400
76800
NOTE
Use the same baud rate for all controllers on the network segment.
6
Set DIP switch 8 to
Off
.
7
Apply power to the Room Controller.
8
Verify communication with the network by viewing a Module Status report in
WebCTRL.
To this model's
Rnet port...
You can wire these combinations of RS room sensors...
RC642
•
1 RS Plus, RS Pro, or RS Pro-F
•
1–3 RS Standards
•
1–3 RS Standards, and 1 RS Plus, RS Pro, or RS Pro-F
RC642D
1-4 RS Standards
See the following sections for wiring instructions. For other details, see the
RS Room
Sensors Technical Instructions
NOTE
Use the specified type of wire and cable for maximum signal integrity.
Description
4 conductor, shielded or unshielded, CMP, plenum rated cable
Conductor
22 AWG (7x0096) bare copper if Rnet has only RS sensors.
18 AWG (7x0152) bare copper if Rnet has a BACview.
Maximum length
500 feet (152 meters)
Insulation
Low-smoke PVC (or equivalent)
Color Code
Black, white, green, red
Wiring an RS room sensor to the Room Controller
Rnet wiring
specifications