![Automated Logic RC642 Technical Instructions Download Page 40](http://html.mh-extra.com/html/automated-logic/rc642/rc642_technical-instructions_3021520040.webp)
36
12
Click
Download Selected Items
.
NOTE
If the download fails, the Room Controller appears in the
Failures
box. Since
this indicates a system problem, do not clear the failure. Locate and resolve the
problem, then retry the download. To retry, select the controller in the
Failures
box,
then repeat steps 4 and 5 above.
13
After the download is complete, set DIP switch 8 to
On
.
14
Cycle the Room Controller's power off, then on again.
1
Remove power from the Room Controller.
2
Set DIP switches 5 and 6 as needed.
To have the Room Controller's
default screen show...
Set DIP switch 5 to...
Time
On
Temp
Off
To show temperatures as...
Set DIP switch 6 to...
Fahrenheit
Off
Celsius
On
3
Apply power to the Room Controller.
NOTE
The Fahrenheit/Celsius setting affects only the display. The control program uses
the units that were set up in the control program.
To set up a stand-alone RC642D Room Controller
To set display
options