15
6
Connect the analog output wiring to the screw terminals on the Room Controller and
to the controlled device.
0-10 V
+
Gnd
Any AO
7
Apply power to the Room Controller.
1
Remove power from the Room Controller.
2
Set DIP switches 5 and 6 as needed.
To have the Room Controller's
default screen show...
Set DIP switch 5 to...
Time
On
Temp
Off
To show temperatures as...
Set DIP switch 6 to...
Fahrenheit
Off
Celsius
On
3
Apply power to the Room Controller.
NOTE
The Fahrenheit/Celsius setting affects only the display. The control program uses
the units that were set up in the control program.
To set display options for a networked RC642D Room Controller