![Automated Logic RC642 Technical Instructions Download Page 27](http://html.mh-extra.com/html/automated-logic/rc642/rc642_technical-instructions_3021520027.webp)
23
The
Switch and Jumper Positions
page shows the current physical settings on the Room
Controller.
The
Display Options
page shows the current selections for the information displayed in
the RC642D Room Controller. On this page, you can choose to have:
•
Time displayed as
12 Hour or 24 Hour format
•
Date displayed as
MM-DD or DD MM format
NOTE
You can also change the format on the RC642D.
1
Tap the
TIME
button until the display shows the item whose format you want to
change, then hold down the
TIME
button.
2
While holding down the button, tap
or
to select a different format.
Using a computer and a USB Link Kit, you can communicate locally with the Room
Controller to download or to troubleshoot.
PREREQUISITES
•
A computer with a USB port
•
A USB Link Kit. See the
USB Link Kit Technical Instructions
The USB Link Kit driver is installed with WebCTRL v5. But if needed, you can
get the latest driver from http://accounts.automatedlogic.com/download. Install the
driver before you connect the USB Link Kit to your computer.
•
v2.09.320 or later controller driver
•
Room Controller is set for network operation (DIP switch 8 is Off).
CAUTION
If multiple controllers share power but polarity was not maintained when they
were wired, the difference between the controller's ground and the computer's AC power
ground could damage the USB Link Kit and the controller. If you are not sure of the wiring
polarity, use a USB isolator between the computer and the USB Link Kit. Purchase a USB
isolator online from a third-party manufacturer.
Switch and
Jumper Positions
Display Options
To communicate through the local access port