9
3
Connect the transformer wires to the
Com
and
24 Vac
screw terminals.
24
Va
c
Com
Run LED
Power LED
98
7 6 5 4
32
1
0
98
7 6 5 4
32
1
0
1 2 3 4 5 6 7 8
O
N
4
Apply power to the Room Controller.
5
Measure the voltage at the Room Controller’s power input terminals to verify that the
voltage is within the operating range of 21.6–26.4 Vac.
6
Plug the terminal connector into the back of the Room Controller.
7
Verify that the
Power
LED is on and the
Run
LED is blinking.
You must give the Room Controller an address that is unique on the network. You can
address the Room Controller before or after you wire it for power.
1
If wired for power, remove power from the Room Controller. The Room Controller
reads the address each time you turn it on.
2
Using the rotary switches, set the address to match the
Address
in the Room
Controller's
Device Properties
dialog box in SiteBuilder. Set the
10's
switch to the tens
digit of the address, and set the
1's
switch to the ones digit.
EXAMPLE
If the address is 25, point the arrow on the
10's
switch to 2 and the arrow
on the
1's
switch to 5.
10’s
1’s
98
7 6
5
4 3
21
0
98
7 6
5
4 3
21
0
1 2 3 4 5 6 7 8
O
N
To address the Room Controller