www.atestgaz.pl
9
Technical specification
Power supply
• V
CC
• Power consumption
15 – 50 V
2.5 W
Environment
• Ambient temperatures
• Humidity
• Pressure
• pH
0 – 50
O
C
10 – 90% long term
0 – 99% short term
1013 ± 10% hPa
5,5 – 7
IP
IP 20
Digital input parameters
• R
IN
• Inactive (not negated)
• Active (not negated)
10 kΩ
0 – 1 V
10 – 50 V
Any polarisation
Whichever polarization > 1s
Digital output parameters
• Relay
Floating contacts, NO/NC
AC1
: 230 V ~ / 3 A
DC1: 230 V / 0.25 A
DC1: 24 V / 3A
Not protected
Digital communication parameters
• TETA BUS port
• Communication protocol
• GTW port
• Electric standard
• Communication protocol
Teta Bus
RS-485
Modbus ASCII / RTU, 4800 – 115200 b/s, no parity / even parity/ odd
parity, number of bits 7/8 (only for Modbus ASCII)
Integrated signalling equipment (visual)
LCD alphanumerical display 2 x 16
optical LEDs
Integrated signalling equipment (audible)
70 dB, 1 m distance
Protection class
III
Dimensions
See figure 1
Cable glands (cable diameter range)
0.08 – 2.5 mm
2
(cable lugs 2 x 1 mm
2
or 2 x 0.75 mm
2
should be used for double wires)
Enclosure material
Self-extinguishing PPO
Weight
0.4 kg
Mounting
On DIN-35 / TS35
Table 17: Technical specification
2
PN-EN 60947 – Low-voltage switchgear and controlgear.
s. 30|31
User's Manual: POD-051-ENG R02