www.atestgaz.pl
If incorrect password is entered three times a row the logging process is interrupted and locked for five
minutes. Any attempt to access options that are password-protected shall lead to appearing of the following
message:
where X stands for the number of minutes that remained to unlocking of the login access.
5.8
Control unit menu
This menu comprises options that relate to operation and parameters of the Control Unit Module Teta MOD
Control 1 as well as the Teta Gas system.
Description of the display content for that view – see section 5.4.
Option
Description
Factory settings
1. Device info
Presents detailed information about the control unit module,
including:
• revision number and version ID of firmware installed on the
control unit,
• status of control voltage at terminals of output relays (the top line
contains numbers of outputs, the bottom line indicates status of
each output: 1 – active, 0 – inactive),
• status of the device (STATEA and STATEB internal registers).
-
2. History
Makes it possible to change password for the password-protected
level 2 of authorization rights – see details in section 5.8.1.
-
3. Language
Enables change of the HMI language – see details in section 5.8.2.
4. Level 2 password
Makes it possible to change password for the password-protected
level 2 of authorization rights – see details in section 5.7.
Operators must be extremely cautious with change of
the access password to the second level of
authorization. When the password is lost (forgotten)
only the manufacturer is able to set up a new
password.
2000
5. Number of
detectors
Makes it possible to define the number of detectors incorporated into
the system of gas detection. Users are prompted to enter the number
from 1 to 50. Consecutive network addresses are assigned in the
control module memory to corresponding detector channels with the
numbering from 1 onward. One has to make sure that subsequent
detectors have consecutive numbers within the permissible range.
1
6. Number of valve
controllers
Makes it possible to define the number of valve controllers
incorporated into the system of gas detection. Users are prompted to
enter the number from 1 to 8. Consecutive network addresses are
assigned in the control module memory to corresponding controller
channels with the numbering from 51 onward. One has to make sure
that subsequent controllers have consecutive numbers within the
permissible range.
0
s. 22|31
User's Manual: POD-051-ENG R02
Login failed