www.atestgaz.pl
Option
Description
Factory settings
7. Buzzer settings
Enables change of settings for the internal buzzer. The following
parameters can be adjusted (see section 5.6):
• duration of the muting time till the buzzer reactivation for alarms,
• duration of the muting time till the buzzer reactivation after
a defect /error,
• permanent deactivation of the buzzer
10 min
8 h
buzzer active
8. Settings for outputs Makes it possible to select the program for operation of relay outputs
– see details in section 4.1.4.
1
9. GTW settings
Enables communication with other systems, e.g. DCS, SCADA or fire
protection systems. The following parameters can be selected:
• protocol for data transmission
• network address
• transmission rate
• parity control
• frame format (only for the MODBUS ASCII protocol).
MODBUS ASCII
1
19200 bauds
even (E)
7 data bits
10. Logout
Return to the basic (unprotected) level 0 of authorization.
-
Table 13: Menu options and factory settings
5.8.1
History
Upon the appropriate option is selected, the Control Unit Module is able to keep records on historical
events. At one moment of time the historical events for a single detector are displayed:
The history of events can be erased by depressing the
, and then
buttons.
5.8.2
Language
Upon the system power up a user is prompted to select the user manual language.
Two languages are available, i.e.:
• Polish,
• English,
• Slovak.
s. 23|31
User's Manual: POD-051-ENG R02
1: CO : ERR
HIS LPG: A1
Possible messages:
A1 – alarm threshold 1 exceeded
A2 – alarm threshold 2 exceeded
A3 – alarm threshold 3 exceeded 3
ERR – error associated with a specific channel
Change language
Polish