www.atestgaz.pl
7
GTW memory map
Description
Type
/comments
Register
Bit
Description of the bit
Bit
Description of the bit
System status
Flags
40001
0
Monitoring
6
Exp – A1
1
Special status – failure
7
Exp – A2
2
Special status – service
8
Exp – A3
3
Tox – A1
9
External alarm
4
Tox – A2
10 – 15 Unused
5
Tox – A3
Control Unit status
Flags
40002
0
R1
4
R5
1
R2
5
R6
2
R3
6 – 14 Unused
3
R4
15
Failure
Detector 1 – status
Flags
40003
0
The detector is active
3 – 14 Unused
1
No data from detector
15
The detector is active
2
Failure not related to
measuring channels
Detector 1 – channel 1
– status
Flags
40004
0
A1
7
Unused
1
A2
8
Special status: failure
UnderRange
2
A3
9
Special status: failure
SignalToHigh
3
Range exceeded
10
Special status: failure
SignalToLow
4
Special status: warm-up
11
Special status: other failure
5
Special status: test with gas
12 – 14 Unused
6
Special status: simulation
15
Active channel
Detector 1 – channel 1 –
information
Flags
40005
0
Quantum concentration: 0: 1,
1: 0,1
3
Information about range – bit 2
1
Range information - bit 0
(definitions of the values are
given in the table 15)
4 – 15 Unused
2
Information about range – bit
1
Description
Type /
comments
Register
Bit
Description of the bit Bit
Description of the bit
Detector 1 – channel 1 – momentary
concentration
S16
40006
-
-
-
-
Detector 1 – channel 1 – medium concentration S16
40007
-
-
-
-
7
A 16-bit number with a sign.
s. 25|31
User's Manual: POD-051-ENG R02