4.1.3
Communication port TETA BUS
The port is designed for digital transmission based on the Teta Bus protocol and dedicated for devices of the
Teta series. This port also allows you to connect a Control V Valve Controller.
See section 6 for details about the system interconnections.
The transmission line of the port needs a specific polarity. See section 8.4.2 for details.
4.1.4
Relays output
The module has six universal relay outputs. These outputs can adopt one of the two statuses: active or
inactive (the active state means that the voltage has been given to the relay coil). Terminals of relays can
switch over to the following positions:
Figure 4: Relays in active and inactive state
Relays status can be checked by the user interface. Details – see section 5.8. Technical specification of
outputs – see section 17.
The subsequent tables summarize functionalities that can be assigned to relay outputs of the Control Unit
Module Teta MOD Control 1 depending on the specific program of the system operation.
Program 1 (garage)
Output
No.
Functionalities
Conditions for the output activation
Conditions for the output deactivation
R1
ALARM 1
CO/NO
2
The first threshold for CO/NO
2
is exceeded or
EXTERNAL ALARM is activated
The monitored concentration of CO/NO
2
drops
below the first threshold and EXTERNAL ALARM
becomes inactive
R2
ALARM 2
CO/NO
2
The second threshold for CO/NO
2
is exceeded
or EXTERNAL ALARM is activated
The monitored concentration of CO/NO
2
drops
below the second threshold and EXTERNAL
ALARM becomes inactive
R3
ALARM 3
CO/NO
2
The third threshold for CO/NO
2
is exceeded or
EXTERNAL ALARM is activated
The third threshold for CO/NO
2
is exceeded or
EXTERNAL ALARM is activated
R4
ALARM 1
LPG/NG
The first threshold for LPG/NG/H
2
is exceeded
or EXTERNAL ALARM is activated
The first threshold for LPG/NG/H
2
is exceeded or
EXTERNAL ALARM is activated
R5
ALARM 3
LPG/NG
The third threshold for LPG/NG/H
2
is exceeded
or EXTERNAL ALARM is activated
The third threshold for LPG/NG/H
2
is exceeded or
EXTERNAL ALARM is activated
R6
NEGATED
FAILURE
No defects
One of the controlled devices reports a defect (is
in the FAILURE mode) or the control unit module
is deprived power
Table 3: Configuration of relay outputs for the Program 1 of the system operation
2 See figure 4.
s. 10|31
User's Manual: POD-051-ENG R02
COM
NC
NO
COM
NC
NO
Active
Inactive