www.atestgaz.pl
Message
Description
ERR: XXX
Error associated with a communication channel with the specific detector. The error code is a
hexadecimal number with the following meaning of individual bits:
bit 0 – negative drift of the sensor
bit 1 – excessively high level of the sensor signal
bit 2 – insufficiently low level of the sensor signal
bit 3 – other defects
Table 11: Error codes for communication channels with gas detectors
momentary concentration
and average concentration of gas measured in the specific channel
In addition, information about other gas detector states may be displayed
5.5.2
Valve controller view
Message
Description
ERR: XXX
Error associated with valve controller. The error code is a hexadecimal number with the
following meaning of individual bits:
bit 0 – incorrect voltage at the battery terminals
bit 1 – incorrect valve line resistance
bit 2 – incorrect device supply voltage
s. 19|31
User's Manual: POD-051-ENG R02
51: VALVE CTRLS.
OK
Status of the valve controller. Possible messages:
OK
– regular operation of the controller
WAITING FOR DATA…
– the control module is waiting for information
NO TRANSMISSION
– gas detector is not connected
PERFORM TEST
– the valve controller indicates the need to perform
a valve test
ERR: XXX – error associated with a specific valve controller
(see the table below)
1: CHW: 0 ppm
1: SR : 0 ppm
1: NO
TRANSMISSION
Controller adress
Possible messages:
WAITING FOR DATA…
– the control module is waiting for information
NO TRANSMISSION
– gas detector is not connected
ERR: improper conf. MiniDet
– improper settings for the HE parameter for
the detector collaborating with the
Teta MiniDet device