www.atestgaz.pl
Program 2 (hall, a solenoid valve 230 V)
Output
No.
Functionalities
Conditions for the output activation
2
Conditions for the output deactivation
R1
GENERAL ALARM
(VISUAL
DEVICES), locked
The first threshold for CO/NO
2
or LPG/NG/H
2
is
exceeded
See section 4.1.4.1
R2
GENERAL ALARM
(AUDIBLE
DEVICES)
The third threshold for CO/NO
2
or LPG/NG/H
2
is exceeded
See section 4.1.4.2
R3
VALVE 230 V
The third threshold for LPG/NG/H
2
is exceeded See section 4.1.4.3
R4
ALARM 1
GENERAL
The first threshold for CO/NO
2
or LPG/NG/H
2
is
exceeded
The monitored concentration of CO/NO
2
or
LPG/NG/H
2
drops below the first threshold
R5
ALARM 3
GENERAL
The third threshold for CO/NO
2
or LPG/NG/H
2
is exceeded
The monitored concentration of CO/NO
2
or
LPG/NG/H
2
drops below the third threshold
R6
NO DEFECTS
None of the controlled devices reports a
defect (is in the FAILURE mode)
At least one of the devices within the controlled
system reports a defect or no power voltage
supplied to the control module
Table 4: Configuration of relay outputs for the Program 2 of the system operation
Program 3 (hall, a solenoid valve 12 V)
Output
No.
Functionalities
Conditions for the output activation
2
Conditions for the output deactivation
R1
GENERAL ALARM
(VISUAL
DEVICES), locked
The first threshold for CO/NO
2
or LPG/NG/H
2
is
exceeded
See section 4.1.4.1
R2
GENERAL ALARM
(AUDIBLE
DEVICES)
The third threshold for CO/NO
2
or LPG/NG/H
2
is exceeded
See section 4.1.4.2
R3
12 V
VALVE
ACTIVATION
The third threshold for LPG/NG/H
2
is exceeded
The monitored concentration of LPG/NG/H
2
drops
below the third threshold
R4
ALARM 1
GENERAL
The first threshold for CO/NO
2
or LPG/NG/H
2
is
exceeded
The monitored concentration of CO/NO
2
or
LPG/NG/H
2
drops below the first threshold
R5
ALARM 3
GENERAL
The third threshold for CO/NO
2
or LPG/NG/H
2
is exceeded
The monitored concentration of CO/NO
2
or
LPG/NG/H
2
drops below the third threshold
R6
NO DEFECTS
None of the controlled devices reports a
defect (is in the FAILURE mode)
At least one of the devices within the controlled
system reports a defect or no power voltage
supplied to the control module
Table 5: Configuration of relay outputs for the Program 3 of the system operation
4.1.4.1 Activation of optical alarm devices
Appropriate configuration of relay outputs makes it possible to control operation of visual alarm devices,
where the devices are activated if the first threshold for the monitored substance is exceeded and
deactivated after the concentration drops below the first threshold or the button
is depressed.
3
Details for connection of a 12 V solenoid valve are provided in the Teta Gas System Manual available at tetagas.atestgaz.pl
s. 11|31