6 knobs are available on PRIMA VA front panel. These knobs can be configured as analog or selector
inputs.
2 opto-isolated voltage inputs are available on PRIMA VA rear panel. These voltage inputs can be
configured as logic inputs only. A 24VDC voltage has to be connected to trigger these inputs.
6.5.1.
To configure logic inputs
§
Click on
Remote Input 1
or
Remote Input 2.
Logic inputs are used to route music or microphone in predefined zones, to trigger messages in
predefined zones, to report third party equipment fault…
Repeat Period
is displayed only if
Repeat Activated Event
option is selected.
Parameter
Access
Description
Mode
Read / Write
Logical (ON / OFF) or Analog or Selector
Normally Closed
Read / Write
Normally open (default) = Active if contact closed
Normally closed = Active if contact open
Monitored
Read / Write
4 states: No connection, Open, Closed, Short-circuit – Fault report if
no connection or short-circuit
Fault when not active
Read / Write
Logic input used as fault report for third party equipment (power
supply, amplifier…)
Repeat Activated
Event
Read / Write
Event is repeated periodically as long as voltage input is active
(incrementation, decrementation…)
Repeat Period
Read / Write
Repetition period, in case Repeat Activated Event option is selected
Confirmation delay
Read / Write
Pulse duration to avoid false input activation
§
Click on Apply changes to save modifications.
§
Click on Back to list to jump to
Basic config > Logic I/O page.