AS64 series AC servo drive Function codes
-165-
P4.98
Mask encoder EEPROM
data faults
Setting
range
Default
Unit
Applicable
mode
0–1
0
-
P
S
T
This parameter specifies whether to mask the fault indicating there is no data or incorrect data on
the EEPROM equipped with the communication encoder.
If fault Er2-c or Er2-d occurs but the motor model is set correctly, you can use the motor after
repower-on. The drive uses the motor data in the EEPROM equipped with the drive for parameter
initialization.
P4.98
Data size
16bit
Data format
DEC
Modbus address
1996, 1997
CANopen address
0x2462, 0x00
6.6 Program Jog, homing, and PTP control (group P5)
6.6.1 Program Jog settings
P5.00
Jog mode
Setting
range
Default
Unit
Applicable
mode
0–6
0
-
P
This parameter specifies the program Jog mode.
Mode
Key
Function
[
0
]
(Wait time P5.04→Forward moving P5.01) × Cycles P5.05
P5.02
Speed 0
P5.04
P5.03 P5.04
P5.04
P5.05
P5.01
P5.01
P5.01
1
(Wait time P5.04→Forward moving P5.01) × Cycles P5.05
P5.02
Speed 0
P5.04
P5.04
P5.05
P5.01
P5.01
P5.01
P5.03
P5.04
2
(Wait time P5.04→Forward moving P5.01) × Cycles P5.05
→(Wait time P5.04→Reverse movingP5.01) × Cycles P5.05
P5.02
Speed 0
P5.04
P5.03 P5.04
P5.04
P5.05
P5.01
P5.01
P5.01
P5.04
P5.04
P5.05
P5.01
P5.01
P5.01
P5.04
P5.02
3
(Wait time P5.04→Reverse moving P5.01) × Cycles P5.05
→(Wait time P5.04→Forward moving P5.01) × Cycles P5.05
P5.02
P5.04
P5.04
P5.04
P5.05
P5.01
P5.01
P5.01
P5.02
Speed 0
P5.04
P5.04
P5.05
P5.01
P5.01
P5.01
P5.03
P5.04