Events and registers
The auto-recloser function (abbreviated "AR" in event block names) generates events and registers
from the status changes in the monitored signals as well as the control command fails and
operations. The user can select which event messages are stored in the main event buffer: ON, OFF, or
both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.4.4 - 211. Event codes.
Event number Event channel
Event block name Event code
Description
4032
63
AR1
0
AR Ready ON
4033
63
AR1
1
AR Ready OFF
4034
63
AR1
2
AR Locked reset
4035
63
AR1
3
AR Reclosing request rejected ON
4036
63
AR1
4
AR Reclosing request rejected OFF
4037
63
AR1
5
AR Reclosing request ON
4038
63
AR1
6
AR Reclosing request OFF
4039
63
AR1
7
User-operated Object AR halted and reset
4040
63
AR1
8
Object failure, AR locked
4041
63
AR1
9
Shot failed
4042
63
AR1
10
AR cycle ends due to a discrimination request
4043
63
AR1
11
AR Shot clear
4044
63
AR1
12
Object "Close" request
4045
63
AR1
13
Object "Open" request
4046
63
AR1
14
Inhibit condition ON
4047
63
AR1
15
Inhibit condition OFF
4048
63
AR1
16
Locking condition ON
4049
63
AR1
17
Locking condition OFF
4050
63
AR1
18
Reserved
4051
63
AR1
19
AR1 Request ON
4052
63
AR1
20
AR1 Request OFF
4053
63
AR1
21
AR2 Request ON
4054
63
AR1
22
AR2 Request OFF
4055
63
AR1
23
AR3 Request ON
A
AQ
Q-F215
-F215
Instruction manual
Version: 2.04
325