Frequency
±15 mHz (U > 30 V secondary)
±20 mHz (I > 30 % of rated secondary)
Operation time
Definite time function operating time setting
0.00…1800.00 s, setting step 0.005 s
Inaccuracy:
- Definite time (I
M
/I
SET
ratio +/- 50 mHz)
±1.5 % or ±110 ms (max. step size: 100 mHz)
Start time and instant operation time (trip):
f
M
/f
SET
ratio +/- 20 mHz (overreach)
<180 ms
f
M
/f
SET
ratio +/- 200 mHz (overreach)
<90 ms
Reset
Reset ratio (frequency limit)
0.020 Hz
Instant reset time and start-up reset
- f
M
/f
SET
ratio +/- 50 mHz
<2 cycles or <60 ms (max. step size: 100 mHz)
No
Notte!
e!
• The frequency is measured two seconds after a signal is received.
9.2.1.16 Line thermal overload protection (TF>; 49F)
Table. 9.2.1.16 - 342. Technical data for the line thermal overload protection function.
Measurement inputs
Current inputs
Phase current inputs: I
L1
(A), I
L2
(B), I
L3
(C)
Current input magnitudes
TRMS phase currents (up to the 31
st
harmonic)
Settings
Time constants τ
1
Time constant value
0.0…500.00 min, step 0.1 min
Service factor (maximum overloading)
0.01…5.00 × I
N
, step 0.01 × I
N
Thermal model biasing
- Ambient temperature (Set –60.0…500.0 deg, step 0.1 deg and RTD)
- Negative sequence current
Thermal replica temperature estimates
Selectable between °C and °F
Outputs
- Alarm 1
- Alarm 2
- Thermal trip
- Trip delay
- Restart inhibit
0…150 %, step 1 %
0…150 %, step 1 %
0…150 %, step 1 %
0.000…3600.000 s, step 0.005 s
0…150 %, step 1 %
Inaccuracy
- Starting
- Operating time
±0.5 % of the set pick-up value
±5 % or ± 500 ms
9.2.1.17 Overpower (P>; 32O), underpower (P<; 32U) and reverse power (Pr; 32R)
protection
Table. 9.2.1.17 - 343. Technical data for the power protection functions.
Measurement inputs