Diagnostics
Document No. D113-015
Page 59 of 77
Revision 1.9
Preambles Required
The minimum number of preambles required by the field device to process
a HART request.
Universal Command Revision
The universal command revision supported by the field device.
Specific Command Revision
The specific command revision supported by the field device.
Software Revision
The software revision of the field device.
Hardware Revision
The hardware revision of the field device electronics.
Function Flags
The Device Function Flags as reported by the field device.
Sensor Minimum Span
The minimum span allowed by the sensor.
Table 5.8 - Channel Status Parameters – Device Info
The Device Status tab displays the status of the analog and HART interaction with the module.
Figure 5.12 - Channel Status – Device Status
Parameter
Description
Loop Open / Current Fault
Flagged if the current loop is either below 3.6mA or above 21.0 mA.
Current Under-range
Flagged if the current is below 3.8mA.
Current Over-range
Flagged if the current is above 20.5 mA.
Loop Shorted
Flagged if a loop short is detected.
Calibration Busy
Flagged when the module is busy being calibrated.
Calibration Failed
Flagged if the calibration data is invalid or corrupt.
HART Comms Fault
Flagged if HART communication is enabled but not active.