Setup
Document No. D113-015
Page 30 of 77
Revision 1.9
Figure 3.29 - RSLogix 5000 General module properties for
HART 4Out
module
NOTE:
The user will need to enter the exact connection parameters before the
module will establish a class 1 connection with the Logix controller.
Next the user needs to add the connection requested packet interval (RPI). This is the rate at
which the input and output assemblies are exchanged. The recommended value is 200ms.
Refer to the technical specification section in this document for further details on the limits
of the RPI.
Figure 3.30 - Connection module properties in RSLogix 5000
Once the module has been added to the RSLogix 5000 I/O tree the user must assign the User
Defined Types (UDTs) to the input and output assemblies. The user can import the required
UDTs by right-clicking on
User-Defined
sub-folder in the
Data Types
folder of the I/O tree and
selecting
Import Data Type
. The assemblies are then assigned to the UDTs with a ladder copy
instruction (COP) as shown in the figure below.