Page 17
EVACU ELITE
INSTALLATION, COMMISSIONING AND USER MANUAL
Outputs 1, 2, 3, 4,
5, 6, 7 and 8
Single ended supervised output/ paired output (voltage reversal), max 2
amps per output and 6 amps per card. Selectable EOL. Output voltage range
12 to 28VDC.
4.2.4.3 Multi-purpose interface card
Occupies one slot
Provides eight supervised inputs, two relay outputs and a high-level interface to the Ampac FireFinder
PLUS
Add On Bus.
Figure 4-15 Multi-purpose interface card
Input 1, 2, 3 and 4 Single ended inputs, common floating reference with selectable EOL
Input 5, 6 and 7
Differential inputs, individual floating reference with selectable EOL
Input 8
Differential input, with floating reference with fault feedback (user selectable
resistance)
Relay 1 and 2
Single pole, double throw (COM, NO, NC)
Serial
RS232C serial port, with CTS and RTS available. Currently unused
FACP
Add On bus connection to the Ampac FireFinder
PLUS
4.2.4.4 Dual 25Watt Amplifier Card
Occupies two slots
Class D amplifier with 2 x 25-watt independent audio outputs with DC monitoring