Page 20
EVACU ELITE
INSTALLATION, COMMISSIONING AND USER MANUAL
Figure 4-19 Quad radial EIS line card
WIP handset 1, 2,
3 and 4
Inputs for Ampac EvacU
ELITE
WIP handsets (polarity insensitive). Up to 2
Ampac MCPs can be connected to each handset. Cabling size
recommended is 1.5mm
2
2 Core,max length 1 km, line impedance 600
Ω,
bandwidth 3K4 Hz.
4.2.4.8 Dual Loop EIS line card
Occupies one slot
Provides 2 individually supervised fault tolerant loop interfaces for handsets and associated manual
call points.
Each loop supports up to 20 handsets with associated manual call points.
Figure 4-20 Dual loop EIS line card
LOOP 1/2 IN/OUT
Inputs for Ampac EvacU
ELITE
Loop WIP handsets. Up to 2 Ampac MCPs
can be connected to each handset. Max of 20 handsets per loop. Cabling
size recommended 1.5mm
2
2 core UTP, max loop length 1000m