Page 77
EVACU ELITE
INSTALLATION, COMMISSIONING AND USER MANUAL
Figure 7-8 24U Cabinet showing the mains isolator, earth point and battery isolator
7.6 Fitting cards to the universal racks
The plug-in cards for the universal rack (see section 4.2.4 and 4.2.5 for a detailed description of the cards) are
packed separately to the cabinet.
The cards should be loaded into the racks as per the site configuration file.
If no configuration file has been created, then the placement of the cards to the racks should be reflected in
the configuration file.
NOTE: Rack 1 is the bottom (lowest rack). Each rack must be fitted with a Distribution CPU. If the configuration
has multiple cabinets (NIC required), the NIC is fixed to the Distribution CPU in rack 1.
7.7 Connecting the batteries
Before connecting the batteries, the battery isolator should be disengaged. The battery isolator is located on
the rear of the cabinet, to the left of the power supply modules. Refer to Fig 7-7 for 13U cabinet and Fig 7-8
for 24U cabinet.