Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
RIS2
2 K
Rise 2
S2MAX
60 °C
Store maximum limitation 2
LST2
ON
Loading store 2
COL 1 >
Collector 1
CEM1
115 °C
Collector emergency temperature 1
OCCO1**
OFF
Option collector cooling 1
CMAX1
95 °C
Maximum collector temperature 1
OCMI1
OFF
Option collector minimum limitation 1
CMIN1
10 °C
Minimum collector temperature 1
OTCO1
OFF
Option tube collector function 1
TCST1
07:00
Tube collector starting time 1
TCEN1
19:00
Tube collector ending time 1
TCRU1
30 s
Tube collector runtime 1
TCIN1
30 min
Tube collector standstill interval 1
OCFR
OFF
Option collector frost protection
CFR O
4 °C
Antifreeze temperature collector on
CFR F
5 °C
Antifreeze temperature collector off
COL 2 >
Collector 2
CEM2
115 °C
Collector emergency temperature 2
OCCO2**
OFF
Option collector cooling 2
CMAX2
95 °C
Maximum collector temperature 2
OCMI2
OFF
Option collector minimum limitation 2
CMIN2
10 °C
Minimum collector temperature 2
OTCO2
OFF
Option tube collector function 2
TCST2
07:00
Tube collector starting time 2
TCEN2
19:00
Tube collector ending time 2
TCRU2
30 s
Tube collector runtime 2
TCIN2
30 min
Tube collector standstill interval 2
LLOGI >
Loading logic
PRIO
Priority logic
PRIO
2
Priority logic
OSTS
OFF
Store set option
TST1
60 °C
Set store temperature store 1
TST2
45 °C
Set store temperature store 2
DTSE
30 K
Spread difference
tLB
2 min
Loading break time
tRUN
15 min
Circulation runtime
PSPEE
OFF
Pause speed option
PDELA
OFF
Pump delay option
OOVRU*
OFF
Overrun option
COOL >
Cooling functions
OSYC**
OFF
System cooling
OSTC
OFF
Store cooling
OHDP**
OFF
Heat dump
DT3 >
Heat exchange
DT3O
6 K
Switch-on difference
DT3F
4 K
Switch-off difference
DT3S
10 K
Set difference
RIS3
2 K
Rise
MAX3O
60 °C
Switch-on temperature (maximum limitation) 86
MAX3F
58 °C
Switch-off temperature (maximum limitation) 86
MIN3O
5 °C
Switch-on temperature (minimum limitation)
MIN3F
10 °C
Switch-off temperature (minimum limitation)
S2DT3
4
Reference sensor heat sink
PUMP >
Pump speed
PUMP1
PULS
Speed variant pump 1
PUMP2
OnOF
Speed variant pump 2
PUMP3
OnOF
Speed variant pump 3
MAN >
Manual mode
MAN1
Auto
Manual mode 1
MAN2
Auto
Manual mode 2
MAN3
Auto
Manual mode 3