AMK Solac 11252 DeltaSol_BX.monen.ind
d
21
|
Level 5
System 7
Solar system with east-/west collectors
The controller compares the temperatures at the collector
sensors S1 and S5 to the store temperature at sensor S2.
If one of the measured temperature differences is higher
than the adjusted switch-on temperature differences, the
corresponding pump (R1, R2) will be activated and the store
will be loaded.
Sensor/Ter-
minal
Designation
Description
S1
TCOL1
Temperature collector 1
S2
TSTB
Temperature store base
S3
Optional sensor for measurement
purposes or options
S4
S5
TCOL2
Temperature collector 2
VFS
Optional sensor for measurement
purposes or options
RPS
V40
Relay
Description
R1
Solar pump collector 1
R2
Solar pump collector 2
R2/R4
optional:
Thermal disinfection
Parallel relay
Heat dump
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
7
System
LOAD >
Loading
DT O
4 K
Switch-on temperature difference
DT F
2 K
Switch-off temperature difference
DT1S
10 K
Set temperature difference
RIS
2 K
Rise
S MAX
75 °C
Store maximum limitation
SMAXS
2
Sensor store max
COL 1 >
Collector 1
CEM1
115 °C
Collector emergency temperature 1
OCCO1**
OFF
Option collector cooling 1
CMAX1
95 °C
Maximum collector temperature 1
OCMI1
OFF
Option collector minimum limitation 1
CMIN1
10 °C
Minimum collector temperature 1
R2
R1
S5
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PWM
2
N
R4
V40
L'
VFS
RPS
out
in