17
|
Level 5
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured tem-
perature differences are higher than the adjusted switch-on
temperature differences, the pump (R1) will be activated and
the corresponding store will be loaded up to the adjusted
maximum temperature via the valve (R3). Store 1 is loaded
with priority.
Sensor/Ter-
minal
Designation
Description
S1
TCOL
Temperature collector
S2
TST1B
Temperature store 1 base
S3
Optional sensor for measurement
purposes or options
S4
TST2B
Temperature store 2 base
S5
Optional sensor for measurement
purposes or options
VFS
RPS
V40
Relay
Description
R1
Solar pump
R2/R4
optional:
Thermal disinfection
Parallel relay
Heat dump
R3
3-port valve store 1 / 2
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
5
System
LOAD1 >
Loading 1
DT1O
4 K
Switch-on temperature difference 1
DT1F
2 K
Switch-off temperature difference 1
DT1S
10 K
Set temperature difference 1
RIS1
2 K
Rise 1
S1MAX
75 °C
Store maximum limitation 1
SMXS1
2
Sensor store max 1
LOAD2 >
Loading 2
DT2O
4 K
Switch-on temperature difference 2
System 5
2-store system with valve logic, 1 pump, 3 sensors and 3-port valve
R3
R1
S4
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PWM
2
N
R4
V40
L'
VFS
RPS
out
in
Note: 3-port valve normally open - store 1 (S2)