
©
AMK Solac 11252 DeltaSol_BX.monen.ind
d
|
40
Level 5
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S4. If the measured
temperature differences are higher than the adjusted switch-
on temperature differences, the pump (R1) will be activated
and the corresponding store zone will be loaded up to the
adjusted maximum temperature via the valve (R3). Store 1
is loaded with priority. Heat exchange from store 1 to store
2 (R2) is possible with another temperature differential
function (S3-heat source/S4-heat sink).
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
16
System
LOAD1 >
Loading 1
DT1O
4 K
Switch-on temperature difference 1
DT1F
2 K
Switch-off temperature difference 1
DT1S
10 K
Set temperature difference 1
RIS1
2 K
Rise 1
S1MAX
75 °C
Store maximum limitation 1
SMXS1
2
Sensor store max 1
LOAD2 >
Loading 2
DT2O
4 K
Switch-on temperature difference 2
DT2F
2 K
Switch-off temperature difference 2
DT2S
10 K
Set temperature difference 2
RIS2
2 K
rise 2
S2MAX
75 °C
Store maximum limitation 2
SMXS2
4
Sensor store max 2
LST2
ON
Loading store 2
Sensor/Ter-
minal
Designation
Description
S1
TCOL
Temperature collector
S2
TST1B
Temperature store 1 base
S3
TSTT
Temperature store 1 top
S4
TST2B
Temperature store 2 base
S5
Optional sensor for measurement
purposes or options
VFS
RPS
V40
Relay
Description
R1
Solar pump
R2
Heat exchange pump
R3
3-port valve store 1 / 2
R4
optional:
Thermal disinfection
Parallel relay
Heat dump
System 16
2-store solar system with valve logic and heat exchange control
R2
R3
R1
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PWM
2
N
R4
V40
L'
VFS
RPS
out
in
Note: 3-port valve normally open
- store 1 (S2)