AMK Solac 11252 DeltaSol_BX.monen.ind
d
35
|
Level 5
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
14
System
LOAD1 >
Loading 1
DT1O
4 K
Switch-on temperature difference 1
DT1F
2 K
Switch-off temperature difference 1
DT1S
10 K
Set temperature difference 1
RIS1
2 K
Rise 1
S1MAX
75 °C
Store maximum limitation 1
SMXS1
2
Sensor store max 1
LOAD2 >
Loading 2
DT2O
4 K
Switch-on temperature difference 2
DT2F
2 K
Switch-off temperature difference 2
DT2S
10 K
Set temperature difference 2
The controller compares the temperature at sensor S1 to
the temperatures at sensors S2 and S3. If the measured tem-
perature differences are higher than the adjusted switch-on
temperature differences, the pump (R1) will be activated and
the corresponding store zone will be loaded up to the adju-
sted maximum temperature via the valve (R3). The priority
logic effects prior loading of the upper zone of the store.
With another temperature differential function (S3-heat
source/S4-heat sink) heating circuit return preheating (hea-
ting circuit backup) is possible via another valve (R2).
System 14
Solar system with store loading in layers and return preheating
R3
R2
R1
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PWM
2
N
R4
V40
L'
VFS
RPS
out
in
Sensor/Ter-
minal
Designation
Description
S1
TCOL
Temperature collector
S2
TSTB
Temperature store base
S3
TSTT/TSTR Temperature store top/
Temp. store return preheating
S4
TRET
Temperature return
S5
Optional sensor for measurement
purposes or options
VFS
RPS
V40
Relay
Description
R1
Solar pump
R2
Return preheating
R3
3-port valve store top/base
R4
optional:
Thermal disinfection
Parallel relay
Heat dump
Note: 3-port valve normally open - store base