AMK Solac 11252 DeltaSol_BX.monen.ind
d
25
|
Level 5
The controller calculates the temperature difference bet-
ween collector sensor S1 and store sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the store will be loaded until the switch-off temperature
difference or the maximum store temperature is reached.
With another temperature differential function (S3/S4)
heating circuit return preheating (heating circuit backup) is
possible via a valve (R2).
Sensor/Ter-
minal
Designation
Description
S1
TCOL
Temperature collector
S2
TSTB
Temperature store base
S3
TSTR
Temp. store return preheating
S4
TRET
Temperature - return
S5
Optional sensor for measurement
purposes or options
VFS
RPS
V40
Relay
Description
R1
Solar pump
R2
Return preheating
R3
optional:
Thermal disinfection
Booster pump
Parallel relay
Heat dump
R4
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
9
System
LOAD >
Loading
DT O
4 K
Switch-on temperature difference
DT F
2 K
Switch-off temperature difference
DT S
10 K
Set temperature difference
RIS
2 K
Rise
S MAX
75 °C
Store maximum limitation
SMAXS
2
Sensor store max
COL >
Collector
CEM
115 °C
Collector emergency temperature
OCCO**
OFF
Option collector cooling
CMAX
95 °C
Maximum collector temperature
System 9
Solar system with 1 store and heating circuit return preheating
R2
R1
S4
S3
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PW
M
2
N
R4
V4
0
L'
VFS
RPS
out
in