The controller compares the temperatures at the collector
sensors S1 and S5 to the temperatures at S2 and S4. If one
of the measured temperature differences is higher than the
adjusted switch-on temperature differences, the correspon-
ding pump (R1, R2) or both pumps will be activated and
the corresponding store will be loaded up to the adjusted
maximum temperature via the valve (R3).
Adjustment channels
Channel
Sub channel 1
Sub channel 2 Factory
setting
Change to
Description
Page
ARR
1
23
System
LOAD1 >
Loading 1
DT1O
4 K
Switch-on temperature difference 1
DT1F
2 K
Switch-off temperature difference 1
DT1S
10 K
Set temperature difference 1
RIS1
2 K
Rise 1
S1MAX
75 °C
Store maximum limitation 1
SMXS1
2
Sensor store max 1
LOAD2 >
Loading 2
DT2O
4 K
Switch-on temperature difference 2
DT2F
2 K
Switch-off temperature difference 2
DT2S
10 K
Set temperature difference 2
Sensor/Ter-
minal
Designation
Description
S1
TCOL1
Temperature collector 1
S2
TST1B
Temperature store 1 base
S3
Optional sensor for measurement
purposes or options
S4
TST2B
Temperature store 2 base
S5
TCOL2
Temperature collector 2
VFS
Optional sensor for measurement
purposes or options
RPS
V40
Relay
Description
R1
Solar pump collector 1
R2
Solar pump collector 2
R3
3-port valve store 1 / 2
R4
optional:
Thermal disinfection
Parallel relay
Heat dump
System 23
Solar system with east-/west collectors and 2 stores (valve logic)
R3
R2
R1
S5
S4
S2
S1
Temp. Sensor
Pt1000
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
VBus
PW
M
1
PWM
2
N
R4
V40
L'
VFS
RPS
out
in
Note: 3-port valve normally open
- store 1 (S2)