AMK Solac 11252 DeltaSol_BX.monen.ind
d
13
|
Level 5
System 3
Solar system with 1 store and afterheating
The controller calculates the temperature difference bet-
ween collector sensor S1 and store sensor S2. If the diffe-
rence is larger than or identical to the adjusted switch-on
temperature difference, the pump (R1) will be switched on
and the store will be loaded until the switch-off temperature
difference or the maximum store temperature is reached.
Domestic hot water afterheating (R4) can be carried out
with a thermostat function (S3). If the value at S3 reaches
the switch-on temperature for the afterheating, the relay is
energised. If the value exceeds the switch-off temperature
for the afterheating, the relay is switched off again.
Sensor/Ter-
minal
Designation
Description
S1
TCOL
Temperature collector
S2
TSTB
Temperature store base
S3
TSTT
Temperature store top
S4
Optional sensor for measurement
purposes or options
S5
VFS
RPS
V40
Adjustment channels
Channel
Sub channel 1
Sub channel 2
Factory
setting
Change to
Description
Page
ARR
1
3
System
LOAD >
Loading
DT O
4 K
Switch-on temperature difference
DT F
2 K
Switch-off temperature difference
DT S
10 K
Set temperature difference
RIS
2 K
Rise
78
S MAX
75 °C
Store maximum limitation
SMAXS
2
Sensor store max
COL >
Collector
CEM
115 °C
Collector emergency temperature
R4
R1
S3
S2
S1
Temp. Sensor
Pt1000