13
5800 SE 78th St. Ocala, FL 34472
Modular HURRiCHiLL Installation & Operations Manual
P: (800) 327-3015
Step
Description
Diagram
12
Use the provided screws to install the
drain pan below the evaporator. Adjust the
condensate diverter (mounted at step 7
above) so the water will dip inside the drain
pan and after that tighten the wing nuts.
Make sure the diverter does not touch the
bottom of the drain pan. Route the drain
line and connect the drain pan to it. When
drilling the opening for the drain through the
panel special precautions should be taken
not to drill through a cam-lock.
The edge of the lock extends 4.25” from the
cam-lock access hole.
13
Connect the refrigeration line sets.
Evaporator assembly cover must be opened
to access line connections.
14
Mount the electric panel on top of the unit.