December 2008
Section 4 Installation
Page 4 – 13
Amerex Restaurant Fire Suppression System (EX 4658)
The cable attaches to the manual pull at the handle by using
set screws. At the MRM, MRM II or PRM the cable attaches to
a cable clamp that is inserted into the fastener on the end of
the manual pull cam. Excess cable must be secured out of the
way of any parts in the module. We suggest taping it to the
manual pull cable.
NOTE: The manual pull cam requires a travel distance of ¾”
to actuate the system. It is not necessary to leave excess
slack in the cable when installing the manual pull station. Any
splices used in the cable must be located at least 12 inches
from the pulley tee or any pulley.
The connector in the
pulley tee should be located as far toward the MRM, MRM
II or PRM as possible
.
TO PULL
STATION #2
TO PULL
STATION #1
TO MRM, MRM II OR PRM