RANGE PROTECTION
SINGLE FLOW POINT NOZZLE (P/N 11982)
RANGE PROTECTION
MULTIPLE NOZZLES (P/N 11982)
December 2008
Section 3 KP Design
Page 3 – 10
Amerex Restaurant Fire Suppression System (EX 4658)
24”Max.
12” Max.
50” Max.
36
”
12”
12”
Note
:
Maximum & minimum heights
must be measured from the tip of nozzle to
the surface of the appliance.
Note:
Maximum & minimum heights must be
measured from the tip of nozzle to the surface of
the appliance.
12" 12"
12'"
24" Max.
12"
50"
For ranges that have a surface area exceeding the
capabilities of a single appliance nozzle, multiple
nozzles must be used provided that the surface area
of the range is divided into equally sized
modules.
Each module must be equal to or less than 12" x 24"
(31 x 61 cm).
The Amerex appliance plenum nozzle (P/N 11982) has
one flow point and will protect a range surface area of
12” x 24” (31 x 61 cm). The center to center distance
between burners must not exceed 12” (31 cm). The
nozzle must be located 36 – 50” (91 - 127 cm) above the
range surface and centered between the two burners.
The range surface area is measured from the outside of
the burner to the outside of the burner.
36"
12"