December 2008
Section 3 KP Design Page 3 - 17
Amerex Restaurant Fire Suppression System (EX 4658)
SOLID FUEL APPLIANCES
NATURAL AND MESQUITE CHARCOALCHARBROILER
ONE AND ONE HALF (1½) FLOW POINT NOZZLE
(P/N 11983)
MESQUITE CHIPS & CHUNKS CHARBROILER
ONE AND ONE HALF (1½) FLOW POINT NOZZLE
(P/N 11983)
MESQUITE LOG CHARBROILER
ONE AND ONE HALF (1½) FLOW POINT NOZZLE
(P/N 11983)
A single Amerex solid fuel appliance nozzle (P/N 11983) will
protect a mesquite log charbroilers with a maximum cooking
surface of 28½ inches X 24 inches (72 cm X 61 cm). The nozzle
uses one and one half (1½) flow points and for this application
must be located between 19 to 44 inches (48 cm to 112 cm)
above the cooking surface anywhere along or within the
perimeter of the appliance aimed at the center of the appliance.
Solid fuel is limited to three (3) layers of logs or 11 inch (28 cm)
maximum stacked height.
A single Amerex solid fuel appliance nozzle (P/N 11983) will
protect a mesquite charbroilers with a maximum cooking
surface of 28½ inches X 24 inches (72 cm X 61 cm). The
nozzle uses one and one half (1½) flow points and for this
application must be located between 16 to 48 inches (41 cm
to 122 cm) above the cooking surface anywhere along or
within the perimeter of the appliance aimed at the center of
the appliance. The fuel depth is limited to 6 inches (15 cm)
maximum,
One Amerex solid fuel appliance nozzle (P/N 11983) will
protect a charcoal charbroilers with a cooking surface
measuring 28½ inches x 24 inches (72 cm x 61 cm)
maximum. The nozzle uses one and one half flow points.
It must be located 16 to 42 inches (41 cm – 107 cm) above
the cooking surface and anywhere along or within the
perimeter aimed at the center. The fuel depth is limited to 6
inches (15 cm) maximum.
42"
16"
24"
28 ½"
6"
Max.
Solid Fuel - Charcoal
48"
16"
28 ½"
24"
6"
Max.
Solid Fuel – Mesquite Chips & Chunks
44"
19"
28 ½"
11"
Max.
Solid Fuel – Mesquite Logs
24"