INSTALLING THE 375 AGENT CYLINDER ASSEMBLY (P/N 13334) TO
P/N 16085 OR P/N 17690 BRACKET ASY.
INSTALLING THE 275 / 375 / 475 AGENT CYLINDER ASSEMBLY (P/N 13334, 16921, or 17379) TO
P/N 16920 BRACKET ASY.
INSTALLING THE MODEL 600 AGENT CYLINDER BRACKET
(P/N 15166 - DISCONTINUED)
(P/N 21583 - DISCONTINUED)
(P/N 23184 – NEW)
Choose an appropriate location for the Agent Cylinder valve assembly
where the pressure gauge can be read, the cylinder can be safely
assessed for recharge and service, is acceptable to the AHJ and has
sufficient structure to accept the weight. Using the bracket as a template,
mark the mounting holes. Use at least three holes for mounting, secure the
bracket loosely with appropriate fasteners, adjust for level and plumb and
fasten securely. The bracket is supplied with a stainless steel strap to hold
the cylinder against the back of the bracket.
A minimum of three holes,
should be used to mount the bracket in any situation.
INSTALLING THE MODEL 600 DISCHARGE FITTING KIT
(P/N 10199)
The discharge fitting kit consists of a brass fitting with an o-ring on one end
and ¾ NPT male threads on the other, and a stainless steel flange for locking
the fitting in place. The discharge fitting should be inserted into the outlet of
the agent cylinder outlet
carefully
, to insure that the o-ring is not damaged –
the o-ring forms the seal between the cylinder and the discharge piping. The
stainless steel flange is then bolted in place to secure the fitting to the valve
outlet.
INSTALLING THE MODEL 600 AGENT CYLINDER
(P/N 15196) – DISCONTINUED CONFIGURATION
The KP600 agent cylinder assembly is fitted with an attachment
bracket that is a component welded to the cylinder assembly. The
attachment bracket is used to attach the cylinder assembly to the
cylinder mounting bracket. The cylinder attachment bracket fits easily
into the upper slotted portion of the mounting bracket. Once inserted
into the slot, it is locked in place by two notched areas in the
attachment bracket. This will prevent cylinder movement from side to
side. Once this is accomplished, the installer's hands are free to
attach the stainless steel strap to secure the cylinder against the
bracket.
NOTE: BOTH THE SHIPPING PLATE AND THE ANTI-RECOIL
PLATE MUST BE REMOVED AT THE TIME OF
INSTALLATION.
December 2008
Section 4 Installation
Page 4 – 2
Amerex Restaurant Fire Suppression System (EX 4658)
Insert the cylinder onto the hanger to rest on the bottom support. Buckle up belly strap and tighten to aid in
support. Insure proper fit of bracket to cylinder loop. Attach distribution piping to valve outlet via swivel
adapter.
O-Ring
P/N 10140
Place the cylinder so that it rest on the bottom support of the bracket. Install stainless steel belly strap and
tighten against the cylinder to aid in support. Attach distribution piping to swivel fitting and then tighten
swivel to cylinder valve outlet.