Technical Information
37
801-9309.doc
24V source & E-stop (CTB1:8-16)
Case: You use internal 24V power supply to drive your remote status signaling (ex.,
LEDs); you include your E-stop switch
Electrical
Touch-pad
Connect to internal solid-state contacts to
complete your indicator signaling (shown);
CTB1:8-9 closure =
Ready
CTB1:10-11 closure =
HeatOn
CTB1:12-13 closure =
Fault
No polarity to these connections; 1A limit
Connect your N.C. E-stop (rated 24V @
3A min.) as shown.
None
Result: Your remote 24Vdc status signals echo E
ASY
H
EAT
status LEDs; E-stop trip halts
RF power output and equipment operation. Reset E-stop to restart E
ASY
H
EAT
at Home
zone.
If no E-stop device is used, CTB1:15-16
must be jumpered
(factory configuration)
for the E
ASY
H
EAT
to operate; this jumper routes all 24Vdc to the controls, display,
etc.
8
10
12
14
16
9
11
13
15
ground
-
+
+
LEDs, resistors and
EStop; your equipment