Be sure to read and understand on the page 3 to 7 “For safety operation” carefully before use
Connecting the wires for the external operation
(continue)
●
5
Connecting the signal wires
Reference to the right diagram, connect the signal wire for alarm
relay.
Advice
During INSPECTION lamp lighting, output alarm with non-voltage
contact from TB1. For using the signal, you can activate the
security alarm(such as warning light or buzzer) The 1
-
2 is a
contact and the 2
-
3 is b contact.
Output contact specifications
:
AC250V max.1A/ DC30V max.2
A
●
6
Wiring the signal wires
Let the signal wire of TB1 and TB2 through the hole with resin film
along inside the inspection door. Pull the signal wire from the hole
with resin film on the lower part in the side of the inspection door
and wire the equipment.
●
7
Closing the electrical equipment cover
Install the electrical equipment cover and fix with four screws.
●
8
Turning on the switch
Turn on the breaker of power distribution panel.
●
9
Activate the external control setting
Operate “External operate setting” of data setting method(refer to
P
.
27
).
TB
1
3
2
1
Output