Press either the Up or Down button to cycle through the settings. When
the desired setting is displayed, press the Test/Reset button. The PGM
descriptor will flash once and the horn will give two quick beeps to
acknowledge the save.
The monitor will return to the P09 Configuration menu selection. Press
the Up and Down Buttons to advance to another Configuration
Parameter. Press and hold the hold the Test/Reset button for 2 seconds
to exit the Configuration menu.
P10 — Relay Output 2
This relay output has contacts that are closed in the non-energized
state. The contacts can be configured to open when the function is
activated or to close when the function is activated or power is lost.
The table below describes the selections:
Relay Function
Setting Displayed
Contact State
Not Used
--.2
Always closed
Alarm Output
CL.2 with horn icon
and red LED
Closed when in
alarm or power is
lost
Alarm Output
OP.2 with horn icon
and red LED
Open when in alarm
Caution Output
CL.2 with horn icon
and yellow LED
Closed when in
caution, alarm, or
when power is lost
Caution Output
OP.2 with horn icon
and yellow LED
Open when in
caution or alarm
Emergency Purge
Output
CL.2 with EMERG
Closed when in
emergency purge or
when power is lost
Emergency Purge
Output
OP.2 with EMERG
Open when in
emergency purge