![Alnor AirGard 335 Owner'S Manual Download Page 33](http://html1.mh-extra.com/html/alnor/airgard-335/airgard-335_owners-manual_2904655033.webp)
31
31
Relay Function
Setting Displayed
Contact State
Not Used
--.1
Always open
Alarm Output
CL.1 with horn icon
and red LED
Closed when in
alarm
Alarm Output
OP.1 with horn icon
and red LED
Open when in alarm
or when power is
lost
Caution Output
CL.1 with horn icon
and yellow LED
Closed when in
caution or alarm
Caution Output
OP.1 with horn icon
and yellow LED
Open when in
caution, alarm, or
when power is lost
Emergency Purge
Output
CL.1 with EMERG
Closed when in
emergency purge
Emergency Purge
Output
OP.1 with EMERG
Open when in
emergency purge or
power is lost