19
19
SECTION 5
Parameter Configuration
General
NOTE:
Configurable parameters are stored to nonvolatile memory of
the instrument and will not be lost when the monitor loses power.
To access the Configuration mode, press and hold the Test/Reset
button until you hear a double beep and see CAL displayed.
NOTE:
This Calibration initialization sequence takes approximately
10 seconds, during which the display will be fully lit (all segments on)
for about 3 seconds and then blank (all segments off) for about 5
seconds before the word CAL appears.
Once this mode is entered, the monitor will stop monitoring the airflow
and display the configuration menu selections. The configuration menu
selections are CAL, P01, P02, P03, P04, P05, P06, P07, P08, P09, P10,
P11, P12 and dEF.
The first menu selection displayed is CAL. To view the other
parameter configuration menu selections, successively press the Up
and Down Buttons (Up to go forward; Down to go backward). When
the desired configuration menu selection is displayed, press the
Test/Reset button to enter. Within a selection, pressing the Up Button
will scroll forward and pressing the Down Button will scroll backward.
To quickly scroll, hold the button. The scrolling will wrap around
when the allowable range is exceeded.
When a configuration menu selection is entered and a setting is
changed, the Test/Reset button must be pressed to save the change. The
PGM descriptor will flash once and the horn will give two quick beeps
to acknowledge the save and the monitor will return to the Parameter
Configuration menu.
IMPORTANT:
If the Test/Reset button is pressed and held for 2
seconds, the change will not be saved; this is signalled via one long
horn beep.
All parameters are configured in the same manner. To exit the
Parameter Configuration menu, press and hold the Test/Reset button
for 2 seconds. The monitor will also time out and exit the Parameter