After this Configuration menu selection is entered, the monitor will
turn on the program mode PGM descriptor and display the current unit
descriptor:
Press the Up or Down Button to toggle between the two settings. When
the desired setting is displayed, press the Test/Reset button. The PGM
descriptor will flash once and the horn will give two quick beeps to
acknowledge the save. The applicable unit descriptor (fpm or m/s) will
then be on during normal run mode.
The monitor will return to the P02 Configuration menu selection. Press
the Up and Down Buttons to advance to another Configuration
Parameter. Press and hold the hold the Test/Reset button for 2 seconds
to exit the Configuration menu.
P03 — Temporary Horn Disable Timer
During an alarm condition, the alarm can be acknowledged by pressing
the Test/Reset button. This temporarily silences the horn. Normally, the
horn will be silenced for the duration of the current alarm condition.
The monitor can be configured to have the horn come back on after a
specified number of minutes or configured so that the horn can not be
silenced at all.
This Configuration Parameter sets the temporary disable timer. After
this Configuration menu selection is entered, the monitor will turn on
the program mode PGM descriptor and display the current value for the
temporary horn disable timer. This timer can be set to a value from 0 to
255. A setting of 255 indicates that when the alarm is temporarily
silenced by pressing the Test/Reset button, the horn will not come on
again until this alarm condition clears and another alarm event occurs.
A setting of 0 is used to prevent silencing of the horn by pressing the
Test/Reset button. Any value between indicates the time, in minutes,
after which when the horn will come back on if the alarm condition has
not been corrected.
For example, if the monitor is configured for a temporary horn disable
time of 10 minutes, the display will show: