The monitor will return to the P04 Configuration menu selection. Press
the Up and Down Buttons to advance to another Configuration
Parameter. Press and hold the hold the Test/Reset button for 2 seconds
to exit the Configuration menu.
P05 — Alarm-to-Caution Transition Delay Timer
The red alarm to yellow caution transition time is the delay period in
seconds that an air flow condition must remain present before the
monitor will go into the appropriate warning zone. This feature
prevents the monitor from toggling back and forth between zones when
a condition is on the border.
This Configuration Parameter sets the alarm-to-caution transition timer.
After this Configuration menu selection is entered, the monitor will
turn on the program mode PGM descriptor and display the current
value for the alarm-to-caution transition timer. This timer can be set
from 0 to 255 seconds.
For example, if the monitor is currently configured for an alarm-to-
caution transition time of three seconds, the display will show:
Press the Up Button to increase the timer value by 1 second or the
Down Button to decrease the timer value by 1 second. When the
desired setting is displayed, press the Test/Reset button. The PGM
descriptor will flash once and the horn will give two quick beeps to
acknowledge the save.
The monitor will return to the P05 Configuration menu selection. Press
the Up and Down Buttons to advance to another Configuration
Parameter. Press and hold the hold the Test/Reset button for 2 seconds
to exit the Configuration menu.