CAL — Calibration
See Section 3 Calibration.
P01 — Digits Enabled/Disabled
The digits can be enabled or disabled using this Configuration
Parameter. It only disables the numeric airflow velocity reading. The
status indicators and icons will not be turned off. After this
Configuration menu selection is entered, the monitor will turn on the
program mode PGM descriptor and, if the digits are disabled, will
show:
If the digits are enabled, one of the following will be displayed
depending on the current unit of measure selected:
Pressing either the Up or Down Button toggles between the two
settings. When the desired setting is displayed, press the Test/Reset
button. The PGM descriptor will flash once and the horn will give two
quick beeps to acknowledge the save. The digits and applicable unit
descriptor (fpm or m/s) will either be on or off during normal run
mode.
The monitor will return to the P01 Configuration menu selection. Press
the Up and Down Buttons to advance to another Configuration
Parameter. Press and hold the hold the Test/Reset button for 2 seconds
to exit the Configuration menu.
P02 — Unit of Measure
The velocity can be displayed either in feet per minute (fpm) or in
meters per second (m/s), with the applicable descriptor (fpm or m/s) on
during normal run mode.