79
Configure the I/O Modules
Chapter 5
Configure the Module
Properties
Follow these steps to configure the general properties of the module.
1. From the I/O configuration tree, double-click the module, such as the
1791ES-IB8XOBV4 module, to see the Module Properties dialog box.
2. Type a unique name for the module.
3. If desired, type a description.
Note the safety network number (SNN). In most cases, you can use the default
that is provided by the programming software. For a detailed explanation of the
safety network number (SNN), see the GuardLogix® Controller Systems Safety
Reference Manual that is listed in the