
Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
75
Chapter
5
Configure the I/O Modules
Use the Studio 5000 Logix Designer® application to configure the modules.
At the bottom of a dialog box, choose Help for information about how to
complete entries in the dialog box. At the bottom of a warning dialog box,
choose Help to get information about that specific error.
Set the IP Address
If the network uses 192.168.1.x, use the rotary switches on the module to set
the last octet of network IP address. Valid numbers range from 001…254.
Figure 31 - Example Network Address
Topic
Page
Add Modules to the I/O Configuration Tree
Configure the Module Properties
Configure the Safety Connections
Save and Download the Module Configuration
WARNING:
When you change switch settings while power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
4
2
6
8
0
X100
X1
X10
4
2
6
8
0
4
2
6
8
0
This example shows the switches set at 163
with a network address being 192.168.1.163.
1791ES Network Address Switches
1732ES Network Address Switches
4
2
6
8
0
X100
X1
X10
4
2
6
8
0
4
2
6
8
0
Summary of Contents for 1732ES-IB12XOB4
Page 6: ...6 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Table of Contents Notes ...
Page 8: ...8 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Summary of Changes Notes ...
Page 174: ...174 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Index Notes ...
Page 175: ......