Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
23
Safety Function Operation
Chapter 1
Safety Outputs
Read this section for information about safety outputs.
Safety Output with Test Pulse
When the safety output is on, the safety output can be test pulsed, as shown in
By using this function, the following can be detected:
• Short circuits between sourcing output signal lines and the power supply
(positive side)
• Short circuits between sinking output signal lines and the power supply
(negative side)
• Short circuits between output signal lines of the same polarity (from
sourcing output to sourcing output or from sinking output to sinking
output)
If an error is detected, the safety output data and individual-safety output
status turns off.
Figure 11 - Test Pulse in a Cycle
ATTENTION:
Serious injury can occur due to the breakdown of safety
outputs. Do not connect loads beyond the rated value to the safety outputs.
Table 4 - Safety Output Test Pulse
Pulse Width
Period
700 μs
600 ms
IMPORTANT
To prevent the test pulse from causing the connected device to
malfunction, pay careful attention to the input response time of the
device.
OUT
On
Off
Typical
700 μs
Typical
600 ms