APPENDIX A
MODULE BOARD AND DISPLAY BOARD REPLACEMENT INSTRUCTIONS
ALL DL3 UNITS
Suburban Applied Products is introducing an updated control board and display for the Dynaline DL3 models DYNA07AC, DYNA09AC
DYNA12AC and DYNA16AC This is effective on production starting with serial number
LH-F164074-0-12
produced on November 26,
2018. These new boards are GREEN to distinguish them from previous controls. The main board is marked part number 92582 and the
display module board is marked with part number 92583. See the photos below to aid in distinguishing the new control board from the
previous version.
OLD Control and Display Circuit Boards (Blue)
NEW Control and Display Circuit Boards (Green)
Service kit K/11022 consists of the main control board and display module. These controls also do not require the recent EMI shield. The
EMI shield, if installed, should be removed and discarded if it is desired to upgrade the controls.
These new control boards and displays must be installed as a set in existing Dynaline DL-3 models currently in service. The new
display is not compatible with, and cannot be used, with older version boards and the new main control board is not compatible
with, and cannot be used, with older version display modules. If either the main board or the display module of older versions
of the controls needs to be replaced, then service kit K/11022 must be used.
The updated controls include a new freeze protection feature that is active when the Dynaline is operated from the on-board thermostat
and controls. The Dynaline model will operate in heat when the temperature drops below about 45°F when the unit is in STANDBY,
HEAT and COOL mode. This mode can be disabled, if desired. If freeze protection is desired when operated from a wall-mount remote
thermostat, a third-party thermostat with the freeze protection feature must be installed separately.
To disable the freeze protection feature, press the “FAN”, “WARMER” and “COOLER” buttons on the keyboard simultaneously. “NP” will
be displayed when freeze protection is disabled and “FP” will be displayed when freeze protection is enabled.
The removal and re-installation of the Dynaline unit as well as the installation of the this kit must be made by a qualified installer, service
agency or the gas supplier.
Installation Instructions
1.
Disconnect the power cord or turn off the unit at the circuit breaker.
2.
Remove the front cover.
3.
Remove the display board and its mounting bracket. Retain the screws. Unplug the patch cord from the module board.
4.
Unplug the 12 position connector from the module board.
5.
Tag then disconnect all of the remaining wires from the module board including low voltage thermostat wires.
6.
Remove the module board from its mounting bracket by prying up all 7 of the board mounting clips. Remove any remaining clips
from the bracket.
7.
Install the replacement module board.
8.
Reconnect all wires to the module board. For reference, see the attached wiring diagrams. The replacement module board is wired
exactly like the original module board.
9.
If remote thermostat is used, slide dip switch #1 to “ON”.
10.
Install the replacement display board and its mounting bracket.
NOTE: The replacement boards must be installed as a pair.
11.
Reconnect the power to the unit and operate the unit through a complete heating cycle, cooling cycle, and check the fan hi and low
speeds.
12.
Replace the front cover.